Infra-red Fire and Heat Detection
SERIES 5000 - AIR BLOWERS
 
 
PRODUCTS More Detail : TECHNICAL MANUAL 5040 BLOWER 5000 AIR FILTER
 
Click image to enlarge CLICK FOR ENLARGED VIEW
5000 BLOWER - AIR FILTER SIDE

 
  Click image to enlarge CLICK FOR ENLARGED VIEW
5000 BLOWER - TOP VIEW

 
 
SINGLE HEAD SYSTEM
INT. DIA.
MAX DUCT LENGTH
IMP.
MET.
5040 2stg
5044 4stg
1 1/4"
32mm
20m / 65'
60m / 195'
1 1/2"
40mm
50m / 163'
140m / 455'
2"
50mm
180m / 585'
520m / 1k7'
TABLE A - SINGLE SENSOR HEAD
DUCT BORE & LENGTH  v's  BLOWER SIZE
 
 

DUAL HEAD SYSTEM
INT. DIA.
MAX DUCT LENGTH
IMP.
MET.
5040 2stg
5044 4stg
1 1/4"
32mm
3m / 10'
12m / 39'
1 1/2"
40mm
7m / 23'
28m / 91'
2"
50mm
25m / 82'
100m / 325'
TABLE B - TWO SENSOR HEADS
DUCT BORE & LENGTH  v's BLOWER SIZE
 
 
Series 5000 Blower Units

Where a suitable “on site” air supply is not readily available Patol 5000 Series air purge units may be employed.
These devices are multistage centrifugal blowers that can be provided in a variety of configurations that accommodate different application requirements such as air delivery volume / pressure, supply voltage and mounting arrangements.
The units are equipped with a removable and washable/replaceable inlet air filter, which protects the blower in normal air input conditions. These filters are not intended to cope with high dust environments (such as within coal conveyor housings) and the inlet should be piped/ducted to a relatively clean air area.
The units are provided with a 2m flexible supply cable for connection at an adjacent junction box. As standard each blower is provided with a length of 45mm I/D hose for coupling inlet and outlet to rigid ducting adaptors.


 
Dual Conveyors - Air Duct Specifications
In coal handling plant applications twin conveyors may be required to be monitored. A single blower may purge both sensors by employing a “T” branch in the air ducting.
 

 
There are limits to the distance that any Air Purge Blower (APB) can deliver the required air to the infra-red sensor which are mainly dependant on the APB specification and duct bore size. Other factors such as ducting surface characteristic and the air temperature/pressure also have an effect.
5000 Series Air Purge units (APBs) are centrifugal blowers available in a variety of multistage configurations. The standard unit is a two stage unit Type 5040, the second most prevalent is the four stage Type 5044.
Tables A & B to the left indicate typical limitations for smooth bore PVC ducting with the worst case air parameters of minus 20°C at sea level pressure. (Warmer Air enables greater distance)
The tables take into account 2m flexible hose connections at Sensor(s), and 1m at the Blower.
 